Monitoring systems (EMS/BMS)
                    	
                    	
                    		
                    		Daily
	- Inspect visible sensors for damage and obstruction.
- Inspect error log.
- Backup log files.
 
Monthly
	- Inspect local reading versus console readings.
- Backup configuration files.
- Inspect cable integrity and lose contacts.
- Inspect time synchronization.
- Review logical access and privileged user permissions.
 
Quarterly
	- Inspect for available firmware/software updates and install where desired.
- Inspect and clean monitoring/control system and console.
- Inspect wiring monitoring/control system and console.
- Review set points.
 
Yearly
	- Inspect sensors and calibrate (note: certain sensors like humidity sensors might require more frequent calibration).
- Inspect labels and signage.